桥架里的“热”你算过吗

文章来源:https://www.sddlqj.cn/   作者:电缆桥架厂家发布时间:2026-11-18 浏览次数:1

返回:行业动态

夏天配电室一开门,热气扑脸。很多人只关心电缆载流量,忘了桥架本身也在“帮倒忙”。桥架不是被动铁皮槽,它直接决定电缆能散多少热。

When the power distribution room opens in summer, the heat hits my face. Many people only care about the current carrying capacity of cables, forgetting that the cable tray itself is also "counterproductive". The cable tray is not a passive iron trough, it directly determines how much heat the cable can dissipate.

梯式桥架通风好,底部镂空,空气能对流。大直径动力电缆、厂房主干线常用它。但梯式不挡灰、不挡水滴,控制细线容易卡横档,得加衬板。

The ladder style bridge has good ventilation, with a hollow bottom for air circulation. It is commonly used for large-diameter power cables and main plant lines. But the ladder style does not block dust or water droplets, and the control line is prone to getting stuck in the crossbar, so a lining plate needs to be added.

base64_image

托盘式带孔底板,兼顾承托和散热。办公楼、普通厂房用得多。开孔率不是越高越好:孔太密,底板强度掉;孔太少,散热和减重都白搭。一般看底部开孔率在合适区间即可,别只听“多孔散热”这种话。

Tray style perforated bottom plate, balancing support and heat dissipation. Office buildings and ordinary factories are commonly used. The higher the opening rate, the better: if the holes are too dense, the strength of the bottom plate will decrease; Too few holes, both heat dissipation and weight loss are useless. Generally, the bottom porosity should be within the appropriate range, don't just listen to words like 'porous heat dissipation'.

槽式全封闭,屏蔽、防尘、防鼠都好,代价是散热差。里面电缆满铺时,温度会比明敷高一截。这时候不能照搬电缆标称载流量,要按规范做降容:动力线通常预留散热余量,弱电虽发热小,也别塞太满。

Fully enclosed slot design provides good shielding, dust prevention, and rodent protection, but at the cost of poor heat dissipation. When the cables are fully laid inside, the temperature will be slightly higher than when exposed. At this point, we cannot simply copy the nominal current carrying capacity of the cable. We need to reduce the capacity according to the specifications: power lines usually reserve heat dissipation allowance, and although weak electricity generates less heat, do not plug it too full.

山东工地还要看季节温差。冬夏温差大,桥架长度会胀缩。直线段超过一定长度要留伸缩节,过墙、过沉降缝不能硬拉。没这细节,夏天拱、冬天裂,支架受剪,螺栓松动。

Shandong construction sites also need to consider seasonal temperature differences. The temperature difference between winter and summer is large, and the length of the bridge will expand and shrink. Expansion joints should be left for straight sections exceeding a certain length, and they should not be forcefully pulled when passing through walls or settlement joints. Without this detail, the arch will arch in summer, crack in winter, the bracket will be sheared, and the bolts will loosen.

再补一条:电缆排列也影响“热”。桥架里电缆别叠成麻花,分层、分束、留气道。动力电缆填充率控在40%到50%,控制电缆可略高,但别顶满。同一桥架强电弱电混放,既干扰又积热,用隔板分开更稳。

Adding another point: Cable arrangement also affects "heat". The cables in the bridge shall not be stacked into Fried Dough Twists, and shall be layered, bunched and air duct reserved. The filling rate of power cables should be controlled at 40% to 50%, and the control cables can be slightly higher, but not fully filled. Mixing strong and weak electricity on the same bridge not only interferes but also accumulates heat, making it more stable to separate them with partitions.

选型时把“散热”单独列一项:什么结构、什么环境、满载运行几小时、检修能不能打开盖板。桥架选对,电缆寿命和供电稳定都多一层保险。

When selecting, list "heat dissipation" separately: what structure, what environment, how many hours of full load operation, and whether the cover can be opened for maintenance. Choosing the right cable tray adds an extra layer of safety to both cable lifespan and power supply stability.

本文由山东桥架友情奉献。更多有关的知识请点击:http://www.sddlqj.cn我们将会对您提出的疑问进行详细的解答,欢迎您登录网站留言.

This article is contributed by Shandong Bridge Friendship. For more information, please click: http://www.sddlqj.cn We will provide detailed answers to your questions. You are welcome to log in to our website and leave a message