机电验收里,电缆桥架非常常被开整改单的,不是板厚不够,也不是跨距太大,而是接地跨接没做对。现场常听到一句话:“螺栓拧紧了不就导通了?”——这话在镀锌桥架上有条件成立,在非镀锌桥架上就是隐患。
In the mechanical and electrical acceptance, the most common reason for issuing rectification orders for cable trays is not due to insufficient plate thickness or excessive span, but rather due to improper grounding and bridging. A common saying heard on site is: "Isn't the bolt tightened to make it conductive?" - This statement is conditional on galvanized cable trays, but it is a hidden danger on non galvanized cable trays.

按 GB 50303 的口径拆开说:
According to the caliber of GB 50303, when disassembled:
镀锌桥架:连接板两端只要各有 不少于 2 个带防松螺帽或防松垫圈的紧固螺栓,可以不另加铜跨接线。前提是“防松件齐”,普通螺母没弹垫的不算。
Galvanized cable tray: As long as there are at least 2 fastening bolts with anti loosening nuts or washers at each end of the connecting plate, copper jumper wires can be omitted. The premise is that the anti loosening parts are complete, and ordinary nuts without spring washers are not included.
非镀锌桥架(喷塑、烤漆、防火涂料):表面不导电,连接板两端建议跨接 ≥4mm² 铜芯软线或铜编织带,而且接触点要刮漆或用刺破垫圈,否则跨了也白跨。
Non galvanized cable tray (spray coating, baking paint, fireproof coating): The surface is non-conductive, and the two ends of the connecting plate must be bridged with ≥ 4mm ² copper core flexible wire or copper braided tape, and the contact points must be scraped with paint or punctured with washers, otherwise it will be useless if crossed.
全线接地:金属桥架及支架全长不少于 2 处接 PE 干线;总长>30m 时,每隔 20–30m 补一个接地点,首尾必接。
Grounding of the entire line: Metal cable trays and supports shall be connected to PE main lines at no less than 2 locations along their entire length; When the total length is greater than 30m, a grounding point should be added every 20-30m, and both ends must be connected.
现场三个高频翻车点:
Three high-frequency tipping points on site:
跨接线绕成“麻花”:感抗变大,泄流能力下降,规范不允许,要短而直。
The jumper wire is wound into "Fried Dough Twists": the inductance becomes larger and the discharge capacity decreases, which is not allowed by the specification. It should be short and straight.
跨接线借连接板固定螺栓压接:非镀锌桥架这么干等于没跨,得用专用接地螺栓或接地孔。
Crossover wires are secured by connecting plates and bolts for crimping: For non galvanized cable trays, this is equivalent to no spans, and special grounding bolts or holes must be used.
切割/钻孔后防腐不补:镀锌层破了不刷富锌漆,两三年从切口锈起,接地连续性跟着断。
Corrosion prevention without repair after cutting/drilling: If the galvanized layer is broken and not coated with rich zinc paint, the continuity of the grounding will be broken after two to three years due to rusting from the incision.
顺手把相邻两项也捎上,验收一起看:
Bring along the adjacent two items and check them together for acceptance:
钢制直线段>30m、铝合金/玻璃钢>15m 设伸缩节,变形缝处设补偿装置,别锁死;
Expansion joints shall be installed for steel straight sections>30m and aluminum alloy/fiberglass sections>15m, and compensation devices shall be installed at deformation joints to prevent locking;
水平支架 1.5–3m,垂直≤2m,弯头、三通、端部 0.3–0.5m 内加固定点。
Horizontal bracket 1.5-3m, vertical ≤ 2m, with fixed points added within 0.3-0.5m of bends, tees, and ends.
桥架这东西,本体合格只是入场券,电气连续+防腐连续+支撑连续三条都闭合,监理才签字。下次班组交底,别只讲“拧紧”,把“哪类桥架免跨、哪类必跨、防松件查几个”写进单子,比事后返工省事得多。
The bridge frame is only an admission ticket if it is qualified. The electrical continuity, anti-corrosion continuity, and support continuity are all closed before the supervisor signs. Next time the team briefing, don't just talk about "tightening", write down "which type of bridge frame is exempt from crossing, which type must be crossed, and how many anti loosening parts to check" in the list, which is much more convenient than reworking afterwards.
桥架跨接别拧螺丝了事
机电验收里,电缆桥架非常常被开整改单的,不是板厚不够,也不是跨距太大,而是接地跨接没做对。现场常听到一句话:“螺栓拧紧了不就导通了?”——这话在镀锌桥架上有条件成立,在非镀锌桥架上就是隐患。In the